Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM06048
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2006 | FRAMING | Approved | IVRS - Inspection :* | |
04/17/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 1,2 & 4 (BEHIND TUB) NOT COMPLIED WITH 2) NEXT FAILURE WILL REFEE |
|
04/14/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RED HEAD ANCHOR BOLTS NOT ALLOWED ON HOLDOWNS PROVIDE EPOXY SPECIAL INSPECTION REPORT 2) OUTSIDE HOSE BIBS REQUIRED ANTI-SIPHON VALVES 3) INTERIOR BEARING WALLS SHOT PINS NOT SPACED PER PLAN 4) SHEAR WALL 9 REQUIRES ANCHOR BOLTS AT 16" ON CENTER 5) ALSO MISSING BEHIND TUB 5) SPLICES IN DBL TOP PLATES MUST BE 48" APART |
|
04/10/2006 | FRAMING | Not ready for Inspection | 1) MARKED ON FLOOR 2) COVER SPAN STUDS 3) NO DWV 4) NO POTABLE H20 5) BANG PLATE ROMEX 6) PROTECT DRYER 7) ITEM 03050 NOT REQUIRED-NO GAS |