Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2007 | ELECTRIC - PROGRESS | Approved | ||
| 10/08/2007 | ELECTRIC - PROGRESS | Not Applicable | IVRS - Inspection :* | |
| 08/08/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK TO POUR POLE BASES (3) |
|
| 08/02/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* INSPECTION FOR CEILINGS MAIN LEVEL -- SECURE FIXTURES TO GRID, CLOSE UP UNUSED RACEWAYS - OK TILES AFTER THAT, OK 2ND LEVEL CEILING TILES. |
|
| 07/24/2007 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* MAIN LEVEL CEILING INSPECTION 1. LOW VOLTAGE WIRING TO BE PROPERLY SUPPORTED FROM STRUCTURE, NOT LAYING ON OR SUPPORTED FROM OTHER EQUIPMENT 2. FINISH FIRE ALARM WIRING 3. SECURE FIXTURES TO GRID - NEC 300.11 4. CHECK J-BOX FILL - NEC 314.16 5. INSTALL ALL J-BOX COVERS 6. STILL NEED TO FINISH WIRING IN THIS AREA DO NOT CALL BEFORE COMPLETE ALSO, DO NOT INSTALL CEILING TILES BEFORE APPROVAL THEY WILL BE REQUIRED TO BE REMOVED NEXT TIME (EXCEPT THOSE NEEDED FOR EQUIPMENT) IT APPEARS AREAS HAVE BEEN COVERED WITHOUT INTERMEDIATE APPROVAL |