Permit: T05CM06045

Parcel: 10705146A

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
12/04/2007 ELECTRIC - PROGRESS Approved
10/08/2007 ELECTRIC - PROGRESS Not Applicable IVRS - Inspection :*
08/08/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK TO POUR POLE BASES (3)
08/02/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
INSPECTION FOR CEILINGS
MAIN LEVEL -- SECURE FIXTURES TO GRID, CLOSE UP UNUSED RACEWAYS - OK TILES AFTER THAT, OK 2ND LEVEL CEILING TILES.
07/24/2007 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
MAIN LEVEL CEILING INSPECTION
1. LOW VOLTAGE WIRING TO BE PROPERLY SUPPORTED FROM STRUCTURE, NOT LAYING ON OR SUPPORTED FROM OTHER EQUIPMENT
2. FINISH FIRE ALARM WIRING
3. SECURE FIXTURES TO GRID - NEC 300.11
4. CHECK J-BOX FILL - NEC 314.16
5. INSTALL ALL J-BOX COVERS
6. STILL NEED TO FINISH WIRING IN THIS AREA DO NOT CALL BEFORE COMPLETE

ALSO, DO NOT INSTALL CEILING TILES BEFORE APPROVAL
THEY WILL BE REQUIRED TO BE REMOVED NEXT TIME (EXCEPT THOSE NEEDED FOR EQUIPMENT) IT APPEARS AREAS HAVE BEEN COVERED WITHOUT INTERMEDIATE APPROVAL