Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
| 06/26/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* POST BOND FOR TEMP POWER 1. IDENTIFY SERVICE DISCONNECT -- NEC 230.70B, ALSO INSTALL ADDRESS ON METER 2. PROPERLY SIZE BOND CONDUCTOR FOR METER BASE AND SERVICE RISER -- NEC 250.66 3. INSTALL FUSES AND PINS 4. CONNECT SERVICE TO GROUNDING ELECTRODE SYSTEM 5. BOND METAL PIPES 6. EXPOSE REPAIR TO G.E.C |