Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T05CM06023
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
02/06/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) PIPING ACCEPTED 2) CONTRACTOR SHALL ENSURE THAT BACKFILL IS IN ACCORDANCE WITH MANUFACTURERS REQUIREMENTS |
|
02/02/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VANGUARD WATER PIPING INSTALLATION SPECIFICATIONS REQUIRE THAT TUBING INSTALLED IN A TRENCH LAY DIRECTLY ON TRENCH BOTTOM AND TRENCH BOTTOM MUST BE SMOOTH AND FREE OF ROCKS AND IRREGULARITIES TUBING MUST BE CONTINUOUSLY SUPPORTED. COT DIRECTIVE DATED 7/16/04 ALLOWS ROCKS UP TO 3/4". 2. COPPER TUBING INSTALLATION SHALL COMPLY WITH THE FOLLOWING CODE SECTIONS 310.3, 606.1.1, 153 PG 291 SEC 316.1.2.3 AND 316.1.2.9 3. CORRECT LEAK AT PRV |
|
12/21/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* NEED TO VIEW PIPE WRAPS PRIOR TO CONCRETE |