Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T05CM06023

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
05/23/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
02/06/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) PIPING ACCEPTED
2) CONTRACTOR SHALL ENSURE THAT BACKFILL IS IN ACCORDANCE WITH MANUFACTURERS REQUIREMENTS
02/02/2006 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VANGUARD WATER PIPING INSTALLATION SPECIFICATIONS REQUIRE THAT TUBING INSTALLED IN A TRENCH LAY DIRECTLY ON TRENCH BOTTOM AND TRENCH BOTTOM MUST BE SMOOTH AND FREE OF ROCKS AND IRREGULARITIES TUBING MUST BE CONTINUOUSLY SUPPORTED. COT DIRECTIVE DATED 7/16/04 ALLOWS ROCKS UP TO 3/4".
2. COPPER TUBING INSTALLATION SHALL COMPLY WITH THE FOLLOWING CODE SECTIONS 310.3, 606.1.1, 153 PG 291 SEC 316.1.2.3 AND 316.1.2.9
3. CORRECT LEAK AT PRV
12/21/2005 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
NEED TO VIEW PIPE WRAPS PRIOR TO CONCRETE