Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | ||
| 04/12/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* OK TO COVER SERVICE RISER NOT ACCEPTABLE. SEE PREVIOUS INSP. |
|
| 04/07/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL VACUUM BREAKERS WHEN WATER LINE IS INSTALLED TO PREVENT THE USE OF UNPROTECTED WATER SUPPLY. REMOVE COLD SOLDIER DRIPPS, REMOVE EXCESS FLUX FROM TUBE. READ UPC INSTALLATION STANDARDS. SEE PAGE 290 READ CAUTION. SEE PAGE 191 ALL SEE UPC SEC. 310 |
|
| 03/23/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* HOSE BIBB VAC BREAKERS REQUIRE BEFORE APPROVAL OF WATER LINE. PROVIDE CLEAN FILL TO 6" AROUND AND ABOVE TUBING. COVER CONTINUOUS LENGTHS W/THIS MATERIAL, LEAVE TRANSITION COUPLINGS UNCOVRED FOR INSPECTIONS. |
|
| 01/12/2006 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* |