Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM06012
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTINGS 2. IDENTIFY PHASE CONDUCTORS 3. DISCONNECT NOT TO BE MOUNTED ON ACCESSIBLE PANELS 440.14 4. USE CORRECT SIZED CONDUCTORS PER FUSE AMPACITY. 5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 |