Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2006 | MECHANICAL - ABOVE CEILING | Approved | PER MECHANICAL FINAL | |
| 03/16/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. REMOTE STATUS PANEL SMOKE ALARMS? 2. ELECT. METER RM. CHECK SUPPLY/EXH GRILLS STATUS 3. OSA GRILL #9 - ALLOWED HOT HUMID/COLD AIR IN UNDER BLDG. ENVELOPE 4. IS ALL NEW FLEX DUCT R-6 AS PER MECH. SPEC'S ITEM #9? |