Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05CM06003
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 08/28/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1. GAS AT MECH. RM. #600 -- GAS FOR #600, #700, #800, #900 AND 1 1/2" STUB IN AT #100 OK 2. ABS DWV AT #700, #800 & #900 OK THRU ROOF 3. COPPER AT #700, #800 & #900 OK HOT INSULATION OK 4. CLOSET FLANGES AND TUBS #700, #800, #900 OK |
|
| 06/02/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* OK TO COVER UNDERGROUND OK PRESSURE TEST. |
|
| 05/30/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. REQUIRE SCOTCH COAT UNDER GRADE - CONTRACTOR TO CLEAN ROCK AND CALICHI FROM TRENCH BEFORE BACKFILLING |
|
| 05/09/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 2 1/2 SCOTCH KOTE FROM EXISTING 3" PLUG VALVE 170' TO EXISTING 2" WITH 14 PSI PRESSURE TEST. PROVIDE CONTINUOUS SUPPORT UNDERPIPING WRAP 3" TEE AND REDUCERS. |