Permit: T05CM05999

Parcel: 141015620

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T05CM05999

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2006 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
06/21/2006 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SPLICES HAVE TO BE CAD WELDED OR SPLICED WITH APPROVED DEVICE YOUR CLAMP IS NOT APPROVED FOR THIS APPLICATION
2) YOU NEED 12" OF COVER AT RISER 90 DEGREE. YOU MAY NEED TO ADD NIPPLE AND COUPLING PER T.E.P. INSPECTOR