Permit: T05CM05994

Parcel: 126211450

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05CM05994

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :
15 PSI TEST FROM METER THRU BUILDING PER PLAN OK
12/01/2006 PLUMBING - GAS PRESSURE TEST Partial Approval
11/30/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
FIND LEAK & RETEST
11/27/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
INTERMINGLING OF CSSE & BLK IRON REQUIRES REVISE APPROVED GAS ISOMETRIC WITH MATERIAL TYPES & DISTANCES CLEARLY STATED & INSTALLED PER THIS REVISED PLAN.
11/15/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SECURE STUB OUTS, SECURE OVERHEAD TUBING
- PROVIDE APPROVED PLAN AND RFI FOR MATERIAL TYPE
- CHECK INSTALLATION INSTRUCTIONS FOR SECURING AND ISOLATION FROM METAL.