Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/27/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* UNABLE TO LOCATE PLAN, PERMIT OR INSPECTION HISTORY. |
|
| 03/23/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* NO PROBLEM FOR TEMP C OF O NEED TO SEE CORRECTION TO URINAL AT FUTURE FOR RECEIVED (8) COPIES OF IN HOUSE BACKFLOW CERTIFICATIONS. |
|
| 03/22/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* OK FOR TEMP C OF O REVISED APPROVED PLAN ON SITE SOME CORRECTIONS ARE MADE. 1. PROVIDE VACUUM BREAKERS AT ALL HOSE BIBS 2. ICE BIN AT WEST BAR TO HAVE CORRECT DRAINAGE 3. ALL FIXTURES TO BE FUNCTIONAL 4. PROVIDE COPIES OF ALL BACKFLOW CERTIFICATIONS 5. PROVIDE CORRECT CRITICAL LEVEL ON URINAL FLUSH VALVES. |
|
| 03/17/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE ITEMS FROM 3/16/06 INSPECTION SPOKE WITH TOM, PLUMBING CONTRACTOR ON SITE ABOUT CORRECTIONS THAT ARE NOT LISTED AND THE NEED FOR REVISED APPROVED PLANS. |
|
| 03/16/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT GAS PIPING AT WATER HEATER & ROOFTOP 2. PROVIDE COPIES OF ALL IN HOUSE BACKFLOW CERTIFICATIONS 3. DRAINS FROM ICE MACHINE TO BE SEPARATE FULL SIZE TO FLOOR RECEPTOR 4. PROVIDE MINIMUM 1" AIR GAP AT ALL INDIRECT DRAIN TERMINATIONS 5. 3-COMP SINKS TO HAVE WASH RINSE INDIRECT SEPARATE FROM SANITIZE DRAIN. 6. YOUR FLOOR PLAN NEEDS TO REFLECT PLUMBING FIXTURES ON SITE. 7. SPOKE TO MECHANICAL INSPECTOR YOU NEED INTERMEDIATE & FINAL MECHANICAL INSPECTION ADDED TO YOUR PERMIT. MAY NOT BE A COMPLETE LIST |
|
| 02/27/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL PLUMBING WORK, HAVE ALL FIXTURE CONNECTION COMPLETE, HAVE ALL APPLIANCES INSTALLED |
|
| 01/06/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*DWV WATER TEST FOR RELOCATED P-4 @ BAR IN SEATING LOUNGE ALL DELETED FIXTURES AND DRAINS UNDER FLOOR IS OK NOTE: NEW SCOPE OF PLUMBING WORK HAS NOT BEEN STARTED @ THIS TIME C.O HAS BEEN INSTALLED @ EXSISTING URINALS. |