Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*NO VERIFICATION OF LIC ELECT COTNRACTRO AS REQUESTED |
|
| 02/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*NO FURTHER INSPECTIONS UNTIL LETTER RECEIVED | |
| 01/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*USE APPROVED FITTINGS FOR M/C CABLE WE HAVE BROKEN SHEATHING/ARMOR ON M/C CABLES SUPPORT M/C WITHIN 12'' OF BOXES PROTECT CABLES AT STUDS JUNCTION BOXES TO BE ACCESSIBLE FILL UNUSED OPENINGS BOX OVER FILL AT SMALL CANS BATHROOM LIGHTING TO REFLECT WORK DONE ALSO DANCE FLOOR |