Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 02/22/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* BIG MAIN BAR NOT INSP 1. CK LARGE MAIN BAR UNDER COUNTER PER RICK H OK TO COVER 2. CK PNL NV PER RICK H -- OK TO COVER 3. SERVICE GUTTER TIE NEW GROUND TO RODS TO NEUTRAL, TIE GROUND PLATE IN GUTTER WITH ALL GROUND (EQUIPMENT) TO GUTTER ENCLOSURE. RECALL INSIDE OK |
|
| 02/13/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/26/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK BATHROOMS 2) ELECTRICAL CONTRACTOR IS TO PROVIDE A LETTER ON COMPANY LETTER HEAD FOR WORK LIABILITY |
|
| 01/25/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT NM CABLES ABOVE PANEL AND DO NTO BUNDLE 2) INSTALL PLASTER RING 3) MISSING EXHAUST FANS 4) SUPPORT M/C WITHIN 12" OF BOXES 5) IS RECEPTACLE IN WALL IN USE ? |
|
| 01/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK DJ STANDS, BAR LEFT, CENTER BAR, LOUNGE, EMPLOYEE BREAKROOM |
|
| 01/05/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |