Permit: T05CM05980

Parcel: 129131480


Addresses:

706 E 32ND ST #01

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/19/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
05/17/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BRASS CLEANOUT INSIDE WALK PRESENTS A SLIGHT TRIPPING HAZARD, CAN YOU GET IT LEVEL?
OTHER HALF OF TWO WAY C/O NEEDS A FEMALE ADAPTER WITH PLUG. CLEANOUT PLUGS SHALL BE WATER & GAS TIGHT.
DISHWASHER HOSE SHALL BE SECURED AS HIGH AS POSSIBLE UNDER KIT. SINK, BUT IN NO CASE LESS THAN 2" BELOW FLOOD LEVEL.
TEST ON SHOWER DRAIN CONNECTION IS DOWN, IT MAY HAVE A LEAK IF A LINER WAS NOT INSTALLED FOR SHOWER PAN
THIS WILL NEED TO BE CORRECTED.
CLEANOUT PLUGS USED TO SECURE COVER SHALL BE DESIGNED AND LISTED FOR SUCH USE. DRILLING OR TAPPING PLASTIC IS PROHIBITED.
05/12/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CALL FOR AND HAVE APPROVED ALL INSPECTIONS PRIOR TO FINAL 3005, 3057, 3040
PROPERLY TRIM OUT ALL CLEANOUTS.
CLEAN OUT INSIDE WALK SHALL BE A BRASS BODY
CLEAN OUT COVER. PROVIDE A TEST ON SHOWER PAN.