Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/28/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/19/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DRIP LEG WATER HEATER 2) ANTI-TILT STOVE 3) NOTES 9, 11 & 12 FROM PREVIOUS 4) PROVIDE 2 CIRCUITS SMALL APPLIANCE KITCHEN 5) SMOKIES NOT INTERCONNECTED 6) ARC FAULT BEDROOM OUTLETS 7) A/C DOES NOT OPERATE |
|
| 05/05/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ROOF AREA NEEDS ROOF JACK H20 HTR FLUE 2) PAINT CONDENSATE 3) A/C DISCONNECT BOX LOOSE 4) 2 UNSHIELDED EXT. LIGHT FIXTURES ALLOWED 5) BUBBLE COVER ON EXT. RECEPTS 6) REAR GAS LINE TERMINATION NEEDS A CAP AND VALVE 7) LABEL ALL CIRCUITS IN SERVICE PANEL 8) ALL WIRE TERMINATIONS TO HAVE WIRE NUTS NOT TAPE 9) WASHER VENT TO GO ABOVE ROOF 10) MISSING VENT FOR KIT SINK 11) DISHWASHER DRAIN TO HAVE AIR GAP, WHERE IS RECEPT FOR DISHWASHER ? 12) NEED 30" SPACE FOR TOILET 15" TO CENTER OF CLOSER FLANGE 13) POWER IS OFF ? 14) STOPPED INSPECTION |
|
| 04/29/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/15/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO POWER TO UNIT 2) INSTALL DISHWASHER 3) SEAL WATER CLOSETS AT BASE 4) SHIELDED LIGHT FIXTURES EXTERIOR PER PLAN 5) COMPLETE KITCHEN SINK 6) STOPPED INSPECTION |