Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T05CM05972
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/05/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. RET. AIR DUCTS ABOVE GRID. REFER TO KEYED NOTE #3 NEED REMOTE INDICATOR. 2. FIRE DAMPER - PLEASE REMOVE RETAINING ANGLE FROM 1 SIDE. HOLE SHOULD BE 1/4" LARGER THAN OPENING AROUND SLEEVE. ANGLES SHOULD HAVE FULL CORNERS. 3. DUCT INSUL. OUTSIDE OF BLDG. ENVELOPE DOES IT MEET R-8?? |
|
| 02/27/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*RECALL NEED ACCESS ACROSS FLOOR SPACE |