Permit: T05CM05972

Parcel: 10321671A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T05CM05972

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/09/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
03/05/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. RET. AIR DUCTS ABOVE GRID. REFER TO KEYED NOTE #3 NEED REMOTE INDICATOR.
2. FIRE DAMPER - PLEASE REMOVE RETAINING ANGLE FROM 1 SIDE. HOLE SHOULD BE 1/4" LARGER THAN OPENING AROUND SLEEVE. ANGLES SHOULD HAVE FULL CORNERS.
3. DUCT INSUL. OUTSIDE OF BLDG. ENVELOPE DOES IT MEET R-8??
02/27/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*RECALL NEED ACCESS ACROSS FLOOR SPACE