Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM05971
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
03/28/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) DBL 2 X STUDS LOAD BEARING BRING DOWN FROM 2ND FLOOR TO 1ST AND BETWEEN FLOORS 2) OK TO LATHE |
|
03/24/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FRONT HEADER REQUIRES 2 2 X 10'S, NEED 2 X 10 HEADER AT TOP OF WINDOW OPENING 2) NAIL OFF (6) SHEAR HORIZONTAL AT N/WEST WALL 4" ON CENTER 3) STRAPS REQUIRED ? 150, 12" ABOVE & BELOW FLOOR 1ST/2ND FLOOR 4) ALL 2/DT2 REQUIRE 16D'S AT PLATE TO FLOOR 8" ON CENTER AND ALL 1/DT2 REQUIRES 16D'S AT PLAT TO FLOOR 4" ON CENTER 5) HUS20 HANGERS AT GIRDER REQUIRED MINIMUM 148 SINKERS HANGER CARRIES 3,035 POUNDS TRUSS WT 917 POUNDS |