Permit: T05CM05971

Parcel: 141091000


Addresses:

6593 E WRIGLEY WY


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM05971

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
03/31/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
03/28/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) DBL 2 X STUDS LOAD BEARING BRING DOWN FROM 2ND FLOOR TO 1ST AND BETWEEN FLOORS
2) OK TO LATHE
03/24/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FRONT HEADER REQUIRES 2 2 X 10'S, NEED 2 X 10 HEADER AT TOP OF WINDOW OPENING
2) NAIL OFF (6) SHEAR HORIZONTAL AT N/WEST WALL 4" ON CENTER
3) STRAPS REQUIRED ? 150, 12" ABOVE & BELOW FLOOR 1ST/2ND FLOOR
4) ALL 2/DT2 REQUIRE 16D'S AT PLATE TO FLOOR 8" ON CENTER AND ALL 1/DT2 REQUIRES 16D'S AT PLAT TO FLOOR 4" ON CENTER
5) HUS20 HANGERS AT GIRDER REQUIRED MINIMUM 148 SINKERS HANGER CARRIES 3,035 POUNDS TRUSS WT 917 POUNDS