Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM05969
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
03/28/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING 1ST/2ND FLOOR STRAPS 2) BRING DBL/STUD LOAD BEARING FROM 2ND TO 1ST FLOOR AND BETWEEN FLOORS |
|
03/24/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) FRONT HEADER REQUIRES 2-2 X 10'S AT TOP OF DBL WINDOW 2) NAIL OFF ALL SHEAR PER SCHEDULE 3) 1ST TO 2ND FLOOR STRAPS 12" ABOVE AND BELOW FLOOR TRUSS 4) 2/DT2 NAIL PLATE 16D'S AT 8" ON CENTER 5) 1/DT2 NAIL PLATE 16D'S AT 4" ON CENTER 6) GIRDER HANGERS UPS HUS26 HOLD 3,035 POUNDS, TRUSS WT 919 POUNDS .148 SINKERS OK 7) CRACK IN TRUSS ROOF 8) BRING ALL LOAD BEARING TRIMMERS FROM ROOF DOWN THRU 2ND FLOOR TO SLAB |