Permit: T05CM05967

Parcel: 141091180


Addresses:

6600 E WRIGLEY WY

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/26/2006 FRAMING Approved IVRS - Inspection :*
04/25/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOLDOWNS NOT INSTALLED AND STUDS NOT NAILED PER REPAIR DOCUMENT
04/18/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MTT 28B HOLDOWNS MUST USE EITHER CAST IN PLACE OR EPOXY SET ANCHOR BOLTS. RED HEAD ANCHORS NOT ALLOWED. SEE 4/SD1 AND ? 3 HOLDOWN SCHEDULE
2) RED HEAD ANCHOR BOLTS LOOSE
04/17/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SUPERINTENDENT