Permit: T05CM05959

Parcel: 12308039A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/11/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1. OK FOR SHEETROCK
2. USE R-5 INSULATION IN SUPPLY JUNCTION BOX & RETURN BOOT
3. ON FINAL BE SURE EXPOSED DUCT IS INSULATED WITH R8, PERMANENTLY I.D EQUIPMENT, ISOLATORS, EXPOSE DATA PLATE, FRESH AIR INTAKES, AIR BALANCE REPORT.
01/03/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FLEX DUCT & DUCT INSULATION MUST BE MIN. R-5
INSIDE BLDG.
2. WHERE IS THE CONDENSATE DRAIN?