Permit: T05CM05959

Parcel: 12308039A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/06/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/14/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CORRECTIONS MADE, WILL NEED TO SEE CORRECT INSTALL OF SHOWER DRAIN & PAN ASSEMBLY WITH TEST.
NOTE: AS OF 12/1/05 PER 2003 UPC WATER HEATER SHALL NOT BE SOLE CONTROL OF HOT WATER SUPPLY TO PUBLIC USE LAVS. PROVIDE STAMPED LETTER FROM ENGINEER GIVING DIRECTION FOR THIS PURPOSE.
07/12/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. ABS DWV PIPE TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT THE END OF BRANCHES; THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
BY PLAN REQUIRES CLEVIS HANGERS OR UNISTOUT
BENT FHA STRAPS NOT APPROVED
VERTICAL ABS TO BE SUPPORTED.
2. HORIZONTAL BY HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP.
3. SUPPORT TRAP ARM CLOSE TO TURNOUT.
4. CLOSET FLANGES REQUIRE STAINLESS STELL OR BRASS SCREWS.
5. ARMAFLEX INSULATION INCOMPLETE AND NOT INSTALLED CORRECTLY.
6. WATER TEST THRU ROOF OK