Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CORRECTIONS MADE, WILL NEED TO SEE CORRECT INSTALL OF SHOWER DRAIN & PAN ASSEMBLY WITH TEST. NOTE: AS OF 12/1/05 PER 2003 UPC WATER HEATER SHALL NOT BE SOLE CONTROL OF HOT WATER SUPPLY TO PUBLIC USE LAVS. PROVIDE STAMPED LETTER FROM ENGINEER GIVING DIRECTION FOR THIS PURPOSE. |
|
| 07/12/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ABS DWV PIPE TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT THE END OF BRANCHES; THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. BY PLAN REQUIRES CLEVIS HANGERS OR UNISTOUT BENT FHA STRAPS NOT APPROVED VERTICAL ABS TO BE SUPPORTED. 2. HORIZONTAL BY HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP. 3. SUPPORT TRAP ARM CLOSE TO TURNOUT. 4. CLOSET FLANGES REQUIRE STAINLESS STELL OR BRASS SCREWS. 5. ARMAFLEX INSULATION INCOMPLETE AND NOT INSTALLED CORRECTLY. 6. WATER TEST THRU ROOF OK |