Permit: T05CM05959

Parcel: 12308039A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ON ROOF
1. SERVICE GFI NOT TRIPPING -- NEC 110.3B
2. DISCONNECT NOT TO BE USED AS PULL BOX -- NEC 312.8
3. PROPERLY SIZE AND TERMINATE GROUNDS IN DISCONNECT NEC 110, 250.122
4. PROPERLY SECURE FLEX & TIGHTEN FITTINGS - NEC 350.30
5. PROPERLY IDENTIFY AC'S AND DISCONNECTS -- NEC 110
6. AC 2 DISCONNECT DOES NOT HAVE PROPER FRONT WORKING CLEARANCE -- NEC 110

INSIDE
1. PANEL DIRECTORY NOT IN -- NEC 408.4
2. WATER HEATER NOT WIRED
3. HAVE OPEN WIRING TO OFFICE DESK
4. HAVE DEAD HALL RECEPTACLE
5. EXIT SIGNS NOT LIGHTING UP ON POWER LOSS
6. HAVE SEVERAL LOOSE RECEPTACLES - NEC 406.4

EXTERIOR
1. NEW LIGHTING NOT IN APPROVED PLANS?
2. BOND GAS PIPE
3. SEAL DISCONNECT HOLES (SERVICE)
11/20/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED TO INSTALL NAIL PLATES FOR MC AS REQUIRED BY NEC 330.17

OK INTERIOR ELECTRICAL COVER AFTER ABOVE CORRECTION.