Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/06/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. NEED REJECTION PIN AND FUSES 2. MEYERS HUB TO BE LISTED FOR GROUNDING AT SERVICE 250.92 3. SUPPORT CONDUIT ABOVE METER TO GUTTER 4. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL 5. IDENTIFY GROUNDING EQUIPMENT CONDUCTOR AT TERMINAL. |
|
| 01/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INTERIOR COVER HAS ALREADY BEEN APPROVED |
|
| 11/20/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |