Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/15/2006 | ELECTRIC - FINAL | Denied | 1. EMERGENCY LIGHTING TO BE FED FROM LIGHTING CKT IN THAT AREA - NEC 700.12(E) AND CHECK FOR PROPER MOUNTING HEIGHT IN SHOP -- PROVIDE INSTALLATION SHEET. 2. PROVIDE ACCESS TO CEILING AREA 3. PROVIDE INSTALLATION BOOK FOR HEATERS 4. NEED BOX EXTENDERS @ RECEPTION COUNTER 5. ON ROOF DISCONNECTS, SELF TAP SCREW NOT ALLOWED FOR GROUND AND REMOVE PAINT. IDENTIFY DISCONNECTS AS IDENTIFIED IN PANEL DIRECTORY. |
|
| 08/31/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |