Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05958

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/15/2006 ELECTRIC - FINAL Denied 1. EMERGENCY LIGHTING TO BE FED FROM LIGHTING CKT IN THAT AREA - NEC 700.12(E) AND CHECK FOR PROPER MOUNTING HEIGHT IN SHOP -- PROVIDE INSTALLATION SHEET.
2. PROVIDE ACCESS TO CEILING AREA
3. PROVIDE INSTALLATION BOOK FOR HEATERS
4. NEED BOX EXTENDERS @ RECEPTION COUNTER
5. ON ROOF DISCONNECTS, SELF TAP SCREW NOT ALLOWED FOR GROUND AND REMOVE PAINT. IDENTIFY DISCONNECTS AS IDENTIFIED IN PANEL DIRECTORY.
08/31/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*