Permit: T05CM05900

Parcel: 129110800


Addresses:

1021 E 24TH ST #01

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/16/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/09/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
BUILDING DRAIN OK - CALL FOR PIPE WRAP INSPECTION
WATER PIPING MUST MEET PLAN SPECS AND MUST BE CONSISTENT THROUGHOUT
SEWER PIPING - PROVIDE 2% SLOPE
CLEAN OUTS SHALL ALLOW CLEANING IN THE DIRECTION OF FLOW - 2 WAY C/O ARE OK
12/07/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SITE PLAN MUST SHOW BUILDING SEWER TERMINATIONS.
1. 2 SEPARATE ADDRESSES THAT SHAPE A SINGLE HCS CONNECTION WILL REQUIRE A JOINT SEWER AGREEMENT.
2. TEST FITTINGS MUST BE INSTALLED IN THE DIRECTION OF FLOW.
3. 2% SLOPE REQUIRED ON WASTE PIPING
4. SEWER & WASTE PIPING MUST BE SHADED, LEAVE FITTINGS EXPOSED TO CHECK FOR LEAKS.
5. 10' HEAD NOT HOLDING, CHECK FOR LEAKS
6. WATER PIPING MATERIAL DOES NOT MEET PLAN SPECS.