Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM05896
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
07/25/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO CHANGE FROM 7/21/06 |
|
07/24/2006 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER PAUL |
|
07/21/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU MUST PROVIDE A 5 PERCENT GRADE (3" IN 5 FEET AWAY FROM THE FOUNDATION FOR A DISTANCE OF 5 FEET ALL AROUND HOUSE SOUTH AND EAST SIDES DO NOT COMPLY |
|
07/20/2006 | BUILDING - FINAL | Cancelled | CANCELLED PER SUPER | |
07/18/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ADDRESS 2) ELECTRIC PANEL REQUIRES-NO WATER BOND LABEL 3) NOT PROPERLY GRADED. MUST HAVE 5 PERCENT PITCH 5 FEET FROM HOUSE 4) A/C DISCONNECT ACCESS OBSTRUCTED BY CONDENSOR 5) 4" CLEARANCE REQUIRED BETWEEN SOIL AND WEEP SCREED 6) STOPPED INSPECTION-TOO MANY ITEMS |