Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/23/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTERIOR OUTLETS MUST BE GFI PROTECTED 2) EXTERIOR SWITCH MUST HAVE DAMP-LOCATION COVER 3) DBL LUGGING BREAKERS IN PANEL NOT ALLOWED 4) COVER OPENING IN DEAD FRONT COVER 5) CAP OPEN KNOCKOUTS IN PANEL 6) SECURE OVERHEAD CONDUCTORS AND COMPLY WITH DRIP LOOP REQUIREMENTS |