Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) 7 PSI TEST ON PVC DRAIN PIPING, CLEANOUTS AND EXPANSION AND JOINT INSTALLED OK 2) TEST ON VTR-OK 3) WATER PIPING-OK |
|
| 12/28/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ABS WASTE PIPING IN GROUND WITH TRAP PRIMER CONNECTION OK WATER TEST TO 10' |
|
| 12/23/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SHALL PROVIDE 2 PIPE DIAMETERS BETWEEN VENT ENTRY AND WORK OF TRAP TO AVOID S-TRAP 2. PROVIDE CORRECT CONNECTION FOR TRAP PRIMOR WITH NO LEAKAGE. |
|
| 12/16/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*17 EVAP COOLERS W/CONTROL WIRING & GFI MAINT.POWER |