Permit: T05CM05864

Parcel: 13414001K

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM05864

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/09/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
02/22/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
PROVIDE AIR OR WATER TEST ON PIPING
02/16/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
AIR TEST WASTE & VENT THRU ROOF & TO POINT OF CONNECTION FOR VENT BOTH AREAS OK
WATER PIPING OK FOR IN WALL AT RESTROOM
1. NEED TO VIEW WATER TIE IN FOR RESTROOM
2. 3" SANITARY DRAINAGE APPREARS TO BE TIED INTO VENT FROM 1ST FLOOR STOOL. PROVIDE PROOF OF WASTE CONNECTION FOR RESTROOM DRAINAGE.
3. BACKFLOW PROTECTION MAY BE REQUIRED FOR ICE MACHINE & COFFEE MAKER IF PROVEN PROOF OF 1" AIR GAP IS NOT OBTAINED
02/16/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
CLOSET FLANGE TO BE SECURED TO FLOOR PROPERLY.