Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 02/22/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* PROVIDE AIR OR WATER TEST ON PIPING |
|
| 02/16/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* AIR TEST WASTE & VENT THRU ROOF & TO POINT OF CONNECTION FOR VENT BOTH AREAS OK WATER PIPING OK FOR IN WALL AT RESTROOM 1. NEED TO VIEW WATER TIE IN FOR RESTROOM 2. 3" SANITARY DRAINAGE APPREARS TO BE TIED INTO VENT FROM 1ST FLOOR STOOL. PROVIDE PROOF OF WASTE CONNECTION FOR RESTROOM DRAINAGE. 3. BACKFLOW PROTECTION MAY BE REQUIRED FOR ICE MACHINE & COFFEE MAKER IF PROVEN PROOF OF 1" AIR GAP IS NOT OBTAINED |
|
| 02/16/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* CLOSET FLANGE TO BE SECURED TO FLOOR PROPERLY. |