Permit: T05CM05856

Parcel: 13323102D


Addresses:

7350 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
10/02/2006 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
04/10/2006 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
HCS TIE IN AT BUILDING OK
SEE PAST NOTES.
04/07/2006 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
AIR TEST FROM MANHOLE THRU 8" AND 6" BUILDING SEWER TO BUILDING.
1. NEED TO VIEW HCS.
04/06/2006 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
FROM 8X6 WYE BRANCH AT INV. 2534.07 TO 11 1/2 DEGREE FITTING DUCTILE IRON THRU CLEANOUT AT INV. 2537.47 THRU TO BUILDING AT 2544.90 6" SEWER BEDDING, SHADING, LAYING PER REDLINE IN TRAILER.
1. NEED AIR TEST & VERIFICATION OF GRADE WITH REVISED APPROVED PLAN AT LATER DATE. COVER AT OWN RISK.
04/04/2006 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
PROVIDE FITTINGS TO MAKE CHANGES OF DIRECTION OR INSTALL PIPING IN WITH MINIMUM DEFLECTION.
04/03/2006 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
8" SDR 35 FROM EXISTING SEWER, NEW MANHOLE 8" TO
INV: 2534.07 6" HEADING SOUTH APP. 20' WITH 8"X6" WYE FOR BRANCH HEADING TO C/O AT INV. 2540.56
BEDDING, SHADING, LAYING OK
TRACER WIRE OK
1. WILL NEED TO SEE AIR TEST, VERIFICATION OF GRADE AT LATER DATE.