Permit: T05CM05856

Parcel: 13323102D


Addresses:

7350 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/03/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH WIRING CHILLER
2. FINISH POLES

OK TEMP C OF O FOR SUITE 210
SUBJECT TO TERMINATION OF S. LONG
10/02/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ITEMS 1, 4, 11
09/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DISCONNECTS NOT TO BE MOUNTED ANY ACCESSIBLE PANEL -- 440.14
2. TIGHTEN LOOSE FITTINGS
3. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
4. MAINTAIN WORKING CLEARANCES IN FRONT OF A/C DISCONNECTS -- 110.26
5. GROUND JUNCTION BOX ENCLOSURE -- 250.148
6. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING -- 250.8 TIME CLOCK
7. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
8. EM AND EXIT LIGHTS TO BE ON CIRCUIT FOR AREA BEING SERVED -- 700.12 -- PRESS TO TEST TO BE ACCESSIBLE AS PER MANUFACTURERS INSTRUCTIONS.
9. DISCONNECT MEANS NEEDED FOR COMM ROOM FAN COIL
10. MAINTAIN WORKING CLEARANCES IN ELECTRIC ROOM
11. SET POLES. HAVE HEADS INSPECTED BEFORE STANDING.