Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/03/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH WIRING CHILLER 2. FINISH POLES OK TEMP C OF O FOR SUITE 210 SUBJECT TO TERMINATION OF S. LONG |
|
| 10/02/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH ITEMS 1, 4, 11 |
|
| 09/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DISCONNECTS NOT TO BE MOUNTED ANY ACCESSIBLE PANEL -- 440.14 2. TIGHTEN LOOSE FITTINGS 3. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 4. MAINTAIN WORKING CLEARANCES IN FRONT OF A/C DISCONNECTS -- 110.26 5. GROUND JUNCTION BOX ENCLOSURE -- 250.148 6. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING -- 250.8 TIME CLOCK 7. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 8. EM AND EXIT LIGHTS TO BE ON CIRCUIT FOR AREA BEING SERVED -- 700.12 -- PRESS TO TEST TO BE ACCESSIBLE AS PER MANUFACTURERS INSTRUCTIONS. 9. DISCONNECT MEANS NEEDED FOR COMM ROOM FAN COIL 10. MAINTAIN WORKING CLEARANCES IN ELECTRIC ROOM 11. SET POLES. HAVE HEADS INSPECTED BEFORE STANDING. |