Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/28/2006 | FRAMING | Not ready for Inspection | ||
| 02/27/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 4 AND 5 FROM PREVIOUS |
|
| 02/22/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEWER ? MUST BE 10 FEET FROM OPEN WINDOW OR 1 FT ABOVE 2) RIDGE ? NOT INSTALLED 3) FIRE STOP POWDER ROOM CHASE 4) HOLDOWN NUTS LOOSE 5) #8 SHEARWALL MUST BE NAILED AT 4" ON EDGES 6) POWDER ROOM TRAP WEIR CANNOT BE ABOVE VENT OPENING 7) DUC BROKEN AT AIR HANDLER 8) DUCT BEND MUST HAVE 1 DIAMETER RADIUS 9) PLUMBING LEAK AT TOILET |