Permit: T05CM05854

Parcel: 140553740

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/01/2006 FRAMING Approved IVRS - Inspection :*
02/28/2006 FRAMING Not ready for Inspection
02/27/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 4 AND 5 FROM PREVIOUS
02/22/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEWER ? MUST BE 10 FEET FROM OPEN WINDOW OR 1 FT ABOVE
2) RIDGE ? NOT INSTALLED
3) FIRE STOP POWDER ROOM CHASE
4) HOLDOWN NUTS LOOSE
5) #8 SHEARWALL MUST BE NAILED AT 4" ON EDGES
6) POWDER ROOM TRAP WEIR CANNOT BE ABOVE VENT OPENING
7) DUC BROKEN AT AIR HANDLER
8) DUCT BEND MUST HAVE 1 DIAMETER RADIUS
9) PLUMBING LEAK AT TOILET