Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/24/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ANCHOR GARAGE PERSONAL DOOR SILL PLATE 2) REPLACE ANCHOR BOLT GARAGE INTERIOR WALL 3) RED HEAD ANCHOR BOLTS LOOSE 4) BLOCK DUCT BOOTS 3 SIDES 5) ANCHOR KITCHEN WALL BY RANGE HOOD |
|
| 04/20/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NO WATER TEST 2) NEED TO PROTECT COPPER LINE IN INTERIOR SHEARWALL (BANG PLATES) 3) OVER NOTCHING ON INTERIOR SHEAR FOR WATER LINES 4) STUDS AROUND HEATER PLATFORM NOT NAILED 5) MISSING NAILS ON SHEARWALL 6) CHAFFING ON WATER LINES WEST WALL KITCHEN |