Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM05821
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
07/26/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) FILL OPEN TRENCH ON PROPERTY 2) FILL OPEN KNOCKOUTS IN PANEL 3) LABEL ALL CIRCUITS IN ELECTRIC PANEL 4) ELECTRIC PANEL DEAD FRONT DOES NOT FIT 5) YOU CALLED FOR GAS TEST. YOU MUST EITHER INSTALL GAS LINE OR HAVE GAS PRESSURE TEST REMOVED FROM YOUR PERMIT 6) STOPPED INSPECTION |