Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM05820
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
08/14/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FILL OPEN KNOCK OUT IN ELECTRIC PANEL 2) LABEL ALL CIRCUITS IN PANEL 3) SMOKE DETECTOR ARC FAULT WILL NOT TRIP 4) REMOVE CUT NAILS FROM FOUNDATION (SAFETY HAZARD) 5) FILL HOLES IN GARAGE CEILING AND WALLS 6) SECURE FLEX CONDUIT WITHIN 12" OF DISCONNECTS 7) MARK HEAT STRIP LABEL ON FAU 8) SEAL FAN DUCT/TAPE |