Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM05817
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2006 | FRAMING | Approved | IVRS - Inspection :* | |
06/13/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BANG PLATES 2) A.B.'S AT SHEARWALLS 3) SEE MARKS ON FLR 4) MISSING BANG PLATE 5) ITEM 03050 NOT REQUIRED/ALL ELECTRIC |
|
06/07/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TRUSS TYPICAL NON BEARING WALL NOT PER DETAIL 11/SD3 2) GABLE END BRACING INCOMPLETE-SEE DETAIL 8/SD3 AND COMPLY 3) A35'S BIRD BLOCKING MISSING NAILS 4) TRUSS SHEAR TRANSFER PER DETAIL 6/SD3 INCOMPLETE 5) NO TEST POTABLE H20 OR DWV 6) TRUSSES NOT INSTALLED AND BRACED PER TRUSS DRAWINGS 7) SHEAR NAILS SET TO DEEP 8) NEED SPECIAL INSPECTION REPORT ON RETRO FIT EPOXIED HOLDOWN BOLTS |