Permit: T05CM05817

Parcel: 140325050


Addresses:

4016 E BIG GAME PL


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM05817

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2006 FRAMING Approved IVRS - Inspection :*
06/13/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BANG PLATES
2) A.B.'S AT SHEARWALLS
3) SEE MARKS ON FLR
4) MISSING BANG PLATE
5) ITEM 03050 NOT REQUIRED/ALL ELECTRIC
06/07/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TRUSS TYPICAL NON BEARING WALL NOT PER DETAIL 11/SD3
2) GABLE END BRACING INCOMPLETE-SEE DETAIL 8/SD3 AND COMPLY
3) A35'S BIRD BLOCKING MISSING NAILS
4) TRUSS SHEAR TRANSFER PER DETAIL 6/SD3 INCOMPLETE
5) NO TEST POTABLE H20 OR DWV
6) TRUSSES NOT INSTALLED AND BRACED PER TRUSS DRAWINGS
7) SHEAR NAILS SET TO DEEP
8) NEED SPECIAL INSPECTION REPORT ON RETRO FIT EPOXIED HOLDOWN BOLTS