Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/27/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AIR INTAKE MUST BE 10 FT FROM SEWER VENT |
|
| 06/26/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSUFFICIENT CRAWL SPACE 2) BENT NAILS UNACCEPTABLE 3) PEX MUST HAVE 12" CLEARANCE TO CAN LIGHTS 4) STUD SHOES REQUIRED AT OVERBORED STUDS-KITCHEN 5) FHA STRAPS REQUIRED AT OVER BORED PLUMBING VENTS-TOP PLATES 6) FRESH AIR INTAKE WITHIN 10' OF PLUMBING VENT 7) GARAGE SHEAR MUST BE NAILED AT TOP PLATE 8) STOPPED INSPECTION-REFEE WILL APPLY |
|
| 06/21/2006 | FRAMING | Denied | IVRS - Inspection : 1) HEATER IN ATTIC ACCESS 2) H.D.'S NOT NAILED 3) MISSING BOLTS GARAGE BOTTOM PLATE 4) SHIM STUDS UNDER BACK WINDOW 5) WIRE PINCHED BETWEEN STUD AT BACK WINDOW 6) STUCCO MESH NOT NAILED ON BACK PORCH AT TOP |
|
| 06/16/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) PLUMBING NOT READY-RECALL |