Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES IDENTIFY HEAT STRIP ON DATA PLATE. |
|
| 09/25/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - PROVIDE A SECONDARY CONDENSATE DRAIN TO A CONSPICUOUS LOCATION. - PROVIDE FUSES IN FAN COIL DISCONNECT. - SECURE DIFFUSERS TO CEILING GRID. |