Permit: T05CM05801

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/09/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*DUCT SMOKE DETECTOR NOT INSTALLED IN PROPER LOCATION OVERFLOW SENSOR STILL NOT WIRED. LOW VOLTAGE CONTROL WIRING STILL NOT CONNECTED. PAY A RE INSPECTION FEE.
02/08/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
01/31/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CONDENSOR BASE ON ROOF NOT PER PLANS OR MALL REQUIREMENTS.
- PROVIDE A DUCT SMOKE DETECTOR AS NOTED ON PREVIOUS INSPECTION.
- COORDINATE WITH MALL OWNER FOR WIRING.
- BROKEN DUCT STILL NOT REPAIRED.
- PROVIDE A LADDER TO INSPECT FAN COIL.
- DRAIN PAN MUST EXTEND 1 1/2" ON ALL SIDES OF FAN COIL.
- WIRE OVERFLOW SWITCH ON SECONDARY DRAIN
- PAY A REINSPECTIN FEE PRIOR TO NEXT INSPECTION
01/25/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
REPOSITION DRAIN PAN TO FIT ENTIRELY UNDER FAN COIL. PROVIDE A PRIMARY DRAIN TO THE LAV. TAILPIECE AS PER PLANS. PROVIDE SECONDARY DRAIN TO A CONSPICUOUS LOCATION. PROVIDE ACCESS TO FAN COIL. NEED TO SEE CONDENSOR ON ROOF. BE SURE ALL DUCT INSULATION IS MIN. R5 - NO CONTRACTOR ON SITE - THE MALL REQUIRES DUCT SMOKE DETECTORS IN ALL AC UNITS. REPAIR EXISTING 8' SPIRAL DUCT ABOVE CEILING.