Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM05801
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/09/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*DUCT SMOKE DETECTOR NOT INSTALLED IN PROPER LOCATION OVERFLOW SENSOR STILL NOT WIRED. LOW VOLTAGE CONTROL WIRING STILL NOT CONNECTED. PAY A RE INSPECTION FEE. | |
02/08/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
01/31/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONDENSOR BASE ON ROOF NOT PER PLANS OR MALL REQUIREMENTS. - PROVIDE A DUCT SMOKE DETECTOR AS NOTED ON PREVIOUS INSPECTION. - COORDINATE WITH MALL OWNER FOR WIRING. - BROKEN DUCT STILL NOT REPAIRED. - PROVIDE A LADDER TO INSPECT FAN COIL. - DRAIN PAN MUST EXTEND 1 1/2" ON ALL SIDES OF FAN COIL. - WIRE OVERFLOW SWITCH ON SECONDARY DRAIN - PAY A REINSPECTIN FEE PRIOR TO NEXT INSPECTION |
|
01/25/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REPOSITION DRAIN PAN TO FIT ENTIRELY UNDER FAN COIL. PROVIDE A PRIMARY DRAIN TO THE LAV. TAILPIECE AS PER PLANS. PROVIDE SECONDARY DRAIN TO A CONSPICUOUS LOCATION. PROVIDE ACCESS TO FAN COIL. NEED TO SEE CONDENSOR ON ROOF. BE SURE ALL DUCT INSULATION IS MIN. R5 - NO CONTRACTOR ON SITE - THE MALL REQUIRES DUCT SMOKE DETECTORS IN ALL AC UNITS. REPAIR EXISTING 8' SPIRAL DUCT ABOVE CEILING. |