Permit: T05CM05800

Parcel: 12201001B


Addresses:

4580 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/22/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) A LETTER IS ATTACHED REGARDING REMOVAL OF QUANTUM 400 TABLES
03/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE VERIFY LISTING FOR EQUIPMENT 110.3
2. PLEASE FINISH PREVIOUS ITEMS
03/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
2. PLEASE CLEAN EXCESS PAINT FROM SURFACES AT PANEL 110.12
3. NEED TO SEE MEDICAL EQUIPMENT FOR CONNECTION AND LISTING AND LABELING.
4. RECEPTACLES IN X-RAY ROOM TO BE AS PER 517 OR REMOVED.
5. WHERE IS RECEPTACLE AT 84" AFF IN LOBBY
6. PROVIDE A LETTER FOR DELEATION OF "IN USE" LIGHTS
7. EM LIGHTING TO BE AS PER 700.12 ON CIRCUIT SERVING AREA.