Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) A LETTER IS ATTACHED REGARDING REMOVAL OF QUANTUM 400 TABLES |
|
| 03/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE VERIFY LISTING FOR EQUIPMENT 110.3 2. PLEASE FINISH PREVIOUS ITEMS |
|
| 03/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 2. PLEASE CLEAN EXCESS PAINT FROM SURFACES AT PANEL 110.12 3. NEED TO SEE MEDICAL EQUIPMENT FOR CONNECTION AND LISTING AND LABELING. 4. RECEPTACLES IN X-RAY ROOM TO BE AS PER 517 OR REMOVED. 5. WHERE IS RECEPTACLE AT 84" AFF IN LOBBY 6. PROVIDE A LETTER FOR DELEATION OF "IN USE" LIGHTS 7. EM LIGHTING TO BE AS PER 700.12 ON CIRCUIT SERVING AREA. |