Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/22/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 517-13 ALL BRANCH CIR'S PER 517.13 513.17 INCLUDING HR'S TO BE IN APPROVED RACEWAY OR CABLE, CIRCUIT ARE INTERRUPPED BY ROMEX NOW, TALKED TO ENG (DESIGNER FOR EE) WHEN PLANS DRAWN -- DID NOT NOTE ROMEX CIR'D EXIST -- OK ON ELECT TO INSULATE & BOARD ONE SIDE OFF OF ALL |