Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T05CM05773
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2007 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
02/05/2007 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR CANCELLED |
|
02/02/2007 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) PVC 3" FROM 90 DEGREE NORTH WEST SIDE OF BLDG TO 3 X 2 XC 3 TEE 3" COPPER TIE IN TO BLDG 2" PVC TO POOL HOUSE TEST 100 PSI 2) TRACER WIRE OK PER RED LINES ON APPROVED PLANS |
|
01/19/2007 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 100+ PSI TEST 3" PVC SCH 40 FROM 10' FROM METER TO 10' FROM BUILDING COPPER STUB OUT WITH TRACER WIRE. 1. SHALL SEE BUILDING CONNECTION & METER, WITH RPB INSTALLATION WITH TEST & TRACER WIRE CONTINUATION. |
|
10/12/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | THIS INSPECTION FOR 3" CW STUBBED UP AND OUT AT SOUTH WEST CORNER 100 PSI AIR TEST APP 5 OK |