Permit: T05CM05773

Parcel: 141353620

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T05CM05773

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2007 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
02/05/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED
02/02/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) PVC 3" FROM 90 DEGREE NORTH WEST SIDE OF BLDG TO 3 X 2 XC 3 TEE 3" COPPER TIE IN TO BLDG 2" PVC TO POOL HOUSE TEST 100 PSI
2) TRACER WIRE OK PER RED LINES ON APPROVED PLANS
01/19/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
100+ PSI TEST 3" PVC SCH 40 FROM 10' FROM METER TO 10' FROM BUILDING COPPER STUB OUT WITH TRACER WIRE.
1. SHALL SEE BUILDING CONNECTION & METER, WITH RPB INSTALLATION WITH TEST & TRACER WIRE CONTINUATION.
10/12/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval THIS INSPECTION FOR 3" CW STUBBED UP AND OUT AT SOUTH WEST CORNER 100 PSI AIR TEST APP 5 OK