Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05773
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NEED TO MARK & LABEL PANELS |
|
04/13/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
04/13/2007 | ELECTRIC - FINAL | Partial Approval | OK FOR EM LIGHTS & EXIT OK FOR TEMP /CO FOR 04-15-07 RECALL FOR REST OF CORRECTIONS AFTER GRAND OPENING WEEKEND. |
|
04/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL EXTENSIONS ON RECEPT BOXES 7 1/4" BACK FROM FINISHED SURFACE. 2. SEAL OPEN KNOCK OUT IN 12 X 12 JUNCTION BOX 3. STRAP MC CABLE AT ATTIC ACCESS WITHIN 12" OF BOX 4. TIGHTEN COVER ON DISCONNECT SWITCH FROM AIR HANDLER. 5. STRAP MC CABLE TO AIR HANDLER 6. ALL BATHROOM RECEPT TO BE GFCI PROTECTED 7. INSTALL COVERS ON 12 X 12 JUNCTION BOXES AT BATHROOM EXHAUST FANS 8. INSTALL WEATHERPROOF RECEPT COVER ON RECEPT OUTSIDE UNDER EVE 9. ROOFTOP RECEPT TO HAVE BUBBLE COVER & NEEDS TO BE WEATHERPROOF. 10. EM LIGHTING & EXITS NOT OPERATING PROPERLY 11. INSTALL TEST BOTTOM & CHARGING INDICATOR LIGHTS FOR ALL EM FIXTURES 12. GROUND BAR AT GUTTER CANNOT BE ATTACHED WITH SHEETMETAL SCREWS. 13. MARK GROUNDS AT PANELS |