Permit: T05CM05773

Parcel: 141353620

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05773

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/20/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/19/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NEED TO MARK & LABEL PANELS
04/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/13/2007 ELECTRIC - FINAL Partial Approval OK FOR EM LIGHTS & EXIT OK FOR TEMP /CO FOR 04-15-07

RECALL FOR REST OF CORRECTIONS AFTER GRAND OPENING WEEKEND.
04/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL EXTENSIONS ON RECEPT BOXES 7 1/4" BACK FROM FINISHED SURFACE.
2. SEAL OPEN KNOCK OUT IN 12 X 12 JUNCTION BOX
3. STRAP MC CABLE AT ATTIC ACCESS WITHIN 12" OF BOX
4. TIGHTEN COVER ON DISCONNECT SWITCH FROM AIR HANDLER.
5. STRAP MC CABLE TO AIR HANDLER
6. ALL BATHROOM RECEPT TO BE GFCI PROTECTED
7. INSTALL COVERS ON 12 X 12 JUNCTION BOXES AT BATHROOM EXHAUST FANS
8. INSTALL WEATHERPROOF RECEPT COVER ON RECEPT OUTSIDE UNDER EVE
9. ROOFTOP RECEPT TO HAVE BUBBLE COVER & NEEDS TO BE WEATHERPROOF.
10. EM LIGHTING & EXITS NOT OPERATING PROPERLY
11. INSTALL TEST BOTTOM & CHARGING INDICATOR LIGHTS FOR ALL EM FIXTURES
12. GROUND BAR AT GUTTER CANNOT BE ATTACHED WITH SHEETMETAL SCREWS.
13. MARK GROUNDS AT PANELS