Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM05773
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
03/01/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ALL PREVIOUS ITEMS |
|
02/27/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT VDV CABLEING 725.6 2. FINISH PREVIOUS ITEMS 1, 2 & 4 |
|
02/23/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* BUILDING LOCKED RECALL INSP. |
|
02/22/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HOW ARE FIXTURES IN CEILING SUPPORTED TO GRID 2. SUPPORT MC CABLE WITHIN 12" OF BOXES (FIXTURE WHIPS OK AT 6') 3. FIRE ALARM MISSING COVER ABOVE F.A PNL 4. ALL FAN BOXES TO HAVE GROUNDS |
|
01/05/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ELECTRIC ABOVE CEILING WHERE HARD LIDS INSTALLED APPROVED. |