Permit: T05CM05773

Parcel: 141353620

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM05773

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2007 ELECTRIC - ABOVE CEILING Approved
03/01/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ALL PREVIOUS ITEMS
02/27/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. SUPPORT VDV CABLEING 725.6
2. FINISH PREVIOUS ITEMS 1, 2 & 4
02/23/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
BUILDING LOCKED
RECALL INSP.
02/22/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HOW ARE FIXTURES IN CEILING SUPPORTED TO GRID
2. SUPPORT MC CABLE WITHIN 12" OF BOXES (FIXTURE WHIPS OK AT 6')
3. FIRE ALARM MISSING COVER ABOVE F.A PNL
4. ALL FAN BOXES TO HAVE GROUNDS
01/05/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
ELECTRIC ABOVE CEILING WHERE HARD LIDS INSTALLED APPROVED.