Permit: T05CM05764

Parcel: 11010312A


Addresses:

3194 N SWAN RD

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
07/16/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
07/03/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES SOUTHEAST PORTION OF BLDG.
05/30/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/04/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
-SUSPENDED ROUGH DUCT. OK TO PROCEED. PROVIDE MIN. 1/8" PER FT SLOPE ON ALL CONDENSATE DRAINS.
-BE SURE TO MAINTAIN ADEQUATE CLEARANCE TO SERVICE FAN COILS (30")
- PLANS REQUIRE COPPER, INSULATED, ON ALL CONDENSATE DRAINS. PROVIDE LETTER FROM ENGINEER IF USING PLASTIC.