Permit: T05CM05764

Parcel: 11010312A


Addresses:

3194 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/20/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/19/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SCIF ROOM #2: CORDS NOT ALLOWED ABOVE CEILING
400.7 & 8
2. FINISH LOBBY RECEPTION
3. WHAT IS HAPPENING WITH GARBAGE DISPOSAL SWITCHES?
4. FINISH A/C DISCONNECTS
07/18/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TO TILE ROOM 239
OK ROOF
OK 2ND ROOF ABOVE CEILING
07/17/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOX & DRY WALL TO BE AS PER 314.21 1/8" AROUND BOX.
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
3. LEAVE OPEN WIRING FOR GARBAGE DISPOSAL SWITCH.
4. UNCOVER STAIRWELL WALL TO INSPECT FLEX CONDUIT AS DISCUSSED.
07/14/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOMS 106-131