Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/18/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/13/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* OK PANEL "AC" & "B" TO TEST POWER |
|
| 07/07/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RECEIVED LETTER FOR GROUNDING OF SPECIAL SYSTEMS. OK 2ND FLOOR HALLS - WEST EXCEPT AS NOTED - ABOVE CEILING . OK CANS TOP OF STAIRWELL (CENTER). 1. SUPPORT VDV CABELING AS CALLED OUT ON PREVIOUS INSPECTIONS. OK PANELS "Y", "U", "V" TO ENERGIZE. |
|
| 06/30/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/29/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. AC DISCONNECT NOT TO BE MOUNTED ON ACCESSIBLE PANELS OF UNITS 440.14 OK ABOVE CEILING 243-249 OK PANEL "ACA" |
|
| 06/21/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK PANEL "D" TO ENERGIZE OK CEILINGS ROOMS 232, 223, 220, 208-209, 206 EXCEPT AS NOTED. OK HARD LIDS CORRIDORS 221, MAIN LOBBY, ENTRANCE WAY, STAIRWELL WEST. 1. FINISH VDV CABELING 2. VERIFY DERATING PER 310.15 |
|
| 06/15/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK LIGHT FIXTURES & CONDUIT ROOMS 233, 235-237 OK VDV CABELING AS PREVIOUSLY NOTED 1ST FLOOR OK WALL ROOM #272 1. FINISH SUPPORTING VDV CABELING 2ND FLOOR. |
|
| 06/13/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK PANEL "A" & "E" AND AREAS ASSOCIATED WITH FOR POWER TESTING. OK ROOMS #211-219 & 221-231 & 234 FOR ELECTRIC - WAITING ON VDV. CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT PROCEDURES |
|
| 06/12/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE ROOM 135X136 EXCEPT AS NOTED OK AC DISCONNECTS 1ST FLOOR 1. VDV CABELING NOT SUPPORTED 725.6, 800.6 |
|
| 06/09/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/07/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/02/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. VDV CABELING TO BE SUPPORTED AS PER 725.6 2. MAINTAIN CLEARANCES IN FRONT OF A/C DISCONNECTS. 3. JUNCTION BOX TO BE ACCESSIBLE. OK TO TILE ROOM #133, 134, 138-152 EXCEPT AS NOTED |
|
| 05/30/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. VDV CABLING TO BE SUPPORTED 725.6 2. A/C DISCONNECT NEED WORKING SPACE (A/C'S) 3. SUPPORT CONDUITS AS PER CODES. 4. BOND DISCONNECT ENCLOSURES OK 2X4' LAY INS ROOMS 109-122, 125-130 |