Permit: T05CM05764

Parcel: 11010312A


Addresses:

3194 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/19/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/30/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PANEL "F" "C"
OK TO TILE ROOMS 254-266
06/29/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/15/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/26/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CANS LOWER ENTRY LOBBY
05/23/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CANS 222 WEST, BATHROOMS 2ND FLOOR
05/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL ROOM 239-261
OK CANS IN SOFFIT 222 EAST, 210
1. SUPPORT M/C CABLE WITHIN 12" OF CAN CONNECTION.
05/15/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK EAST OF COLUMN 15 2ND FLOOR WALLS
04/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK HARD LIDS AND WALLS EXCEPT AT GROUND CONNECTIONS.
04/04/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NEED TO MAKE GROUND CONNECTIONS
2. SUPPORT VDV CABLING IN WALLS 725.6
3. PROTECT M/C CABLE AT BASE PLATE
4. PROTECT PVC AT BASE PLATE
5. FINISH SUPPORTING PANEL CONDUITS
OK TO ONE SIDE