Permit: T05CM05738

Parcel: 13018001J


Addresses:

4010 E 29TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/04/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/31/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
BUSHING IS CUT (THIS IS NOT ACCEPTABLE)
CLEAR BOND LUG TO DISC.
CONNECTINO (REMOVE ENAMEL PAINT)
03/27/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED BUSHINGS ON ALL CONDUIT - NIPPLES WITH #4 OR LARGER CONDUCTORS.
2. SECURE E.M.T WITHIN 3' OF DISCONNECTS
3. INSTALL BONDING SCREW AT 200 AMP EQUIP. GROUNDING BUS BAR.