Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/31/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* BUSHING IS CUT (THIS IS NOT ACCEPTABLE) CLEAR BOND LUG TO DISC. CONNECTINO (REMOVE ENAMEL PAINT) |
|
| 03/27/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED BUSHINGS ON ALL CONDUIT - NIPPLES WITH #4 OR LARGER CONDUCTORS. 2. SECURE E.M.T WITHIN 3' OF DISCONNECTS 3. INSTALL BONDING SCREW AT 200 AMP EQUIP. GROUNDING BUS BAR. |