Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM05738
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/31/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* BUSHING IS CUT (THIS IS NOT ACCEPTABLE) CLEAR BOND LUG TO DISC. CONNECTINO (REMOVE ENAMEL PAINT) |
|
03/27/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED BUSHINGS ON ALL CONDUIT - NIPPLES WITH #4 OR LARGER CONDUCTORS. 2. SECURE E.M.T WITHIN 3' OF DISCONNECTS 3. INSTALL BONDING SCREW AT 200 AMP EQUIP. GROUNDING BUS BAR. |