Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM05728
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
06/27/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Dbl lugging of neutral wires is not allowed Soil rock must be 4" from weep screed A/C condensate not level Seal garage drywall penetration Garage gfci hot when tripped-will not reset Fill open knockouts in disconnect Stopped inspection to many item Third failure. You must pay a reinspection fee No certification of specials inspections |
|
06/26/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REVERSE PITCH ON A/C CONDENSATE 2) SEAL GARAGE WALL PENETRATIONS 3) NO ELECTRIC TO WATER HEATER 4) NO SPECIAL INSPECTION CERTS 5) STOPPED INSPECTION |
|
06/23/2006 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER PAUL |
|
06/21/2006 | BUILDING - FINAL | Denied | NOT COMPLETE |